Circuit Breaker Analyzer & Timer CAT-P

  • Product No:CAT Series
  • Manufacturer:IBEKO Power AB (DV-Power)


Circuit Breaker Analyzer & Timer (CAT) series are standalone or PC controlled digital instruments for circuit breakers’ condition assessment. They enable simultaneous measurements of up to 12 main contacts (4 breaks per a phase) including pre-insertion resistors and 6 auxiliary contacts. CAT series instruments record graphs of both, the open and close coil currents and displacements of the HV and MV circuit breaker moving parts. The main contact channels can also measure the resistance value of the pre-insertion resistors (if present in the circuit breaker).


The user can select any desired operational mode: Close (C), Open (O), Close-Open (C-O), Open-Close (O-C), Open-Close-Open (O-C-O). Test results can be stored in the instrument’s internal memory, an USB memory stick or printed on a thermal printer (optional accessory) in both tabular and graphical form.

CAT instruments are supplied with DV-Win software, which provides full control of all CAT functions from a PC, as well as acquisition and analysis of test results.


Portable (1,4 kg / 3.1 lbs)

Internal battery power supply

Online measurement  (First trip test)

Offline measurement

DC voltage and DC current measurement

Touch screen color display 145 mm (5.7 in)

On-site analysis of test results (overlay up to 4 records in graphical form)

Test results analysis and comparison with results obtained from other CAT instruments using DV-Win software

 

Number of contact inputs: 3 (3 x 1), 1 per phase
Each channel detects Main contacts
- Closed ≤ 10 Ω
- Resistor contacts range 10 Ω to 5 kΩ
- Open ≥ 5 kΩ
Open circuit voltage: 20 V DC
Short circuit current 50 mA

Time measurement resolution:
 0,05 ms for 1 s test duration
(sampling rate 20 kHz)
 0,1 ms for 2 s test duration
(sampling rate 10 kHz)
Time accuracy: 0,05% of the reading ± resolution

DC Current Clamps
 Nominal current: 300 ARMS or 450 A DCPK
 Measuring ranges: 30/300 A
 Frequency range: DC to 20 kHz (-3 dB)

AC Current Clamps
 Measuring Range: 0,05 A to 5 ARMS
 Accuracy: ±3% ±1 mV (from 0,05 A to 0,5 A),±1,5% ±1 mV (from 0,5 A to 1 A), ±1%(from 1 A to 5 A)

DC Voltage Measurement
 Range: ±300 V
 Typical accuracy: ±0,5% RDG ±0,5% FS
 Guaranteed accuracy: ±1% RDG ±1% FS

Handset Power Supply
 12 V DC, 1 A
Inline Power Supply
 Input: 90 – 264 V AC, 50/60 Hz
Internal Battery Supply
 2 x 3,7 V, 2900 mAh rechargeable Li-ion battery
 8 hours under normal usage

Environmental conditions
 Operating temperature:-10 ºC to + 55 ºC / 14 ºF to +131 ºF
 Storage & transportation:-40 ºC to + 70ºC / -40 ºF to +158 ºF
 Humidity 5 % - 95 % relative humidity,non condensing