The C250 Series Power Calibrators are used for effective adjusting and testing of measuring instruments used in power engineering: active and reactive power meters, phase meters, frequency meters, ammeters, voltmeters, transducers of these quantities in single phase configurations. The C250 Calibrator is single phase source of alternating current and voltage. Enables generating alternating voltages with predefined value 240V, alternating currents with predefined values 10A and 20A, frequency with predefined value 50Hz and phase shift with predefined values 0° and 60°. Current output signals and phase shift values are selecting by push-button in local control mode. Actual values of output voltage and current signals, power factor and frequency are simultaneously indicated on LCD display in the C250M Calibrator with additional meter. In remote control mode current, phase shift, operate/standby mode for voltage and current output can be selected by means of external potential free push buttons connected to terminals on rear panel or by standard interface RS232C/USB from PC computers. Instruments under test can safely be connected to the outputs without changing the set values, since the calibrator can be switched to “standby” mode to isolate the output terminals. Series C250 Calibrators has been built in small size and light weight aluminium case.
TECHNICAL PARAMETERS OF OPTIONS C250 and C250M
Parameter | Settings | Measurement | Accuracy | Maximum | ||||||||||||
resolution | Load | |||||||||||||||
Voltage | 240V | ±0.10% of value | 125mA | |||||||||||||
Calibrator | Current | 10A and 20A | ±0.10% of value | 2V@20A | ||||||||||||
Frequency | 50Hz | ±0.02Hz | ||||||||||||||
function | ||||||||||||||||
Phase shift | 0° and 60° | ±0.1° | ||||||||||||||
Active power | ±0.10% of apparent power | |||||||||||||||
Meter function | Voltage | 0.01V | ±0.10% of value | |||||||||||||
Current | 0.001A | ±0.10% of value | ||||||||||||||
only in the | ||||||||||||||||
Frequency | 0.01Hz | ±0.02Hz | ||||||||||||||
C250M | ||||||||||||||||
Power factor | 0.01 | ±0.01 | ||||||||||||||
THD of voltage and current | 0.5% of value | |||||||||||||||
Weight and dimensions (width x height x depth) | 12kg and (371x150x342)mm | |||||||||||||||
Power supply | 230V±10% / 45…65Hz / 180VA |