True Three-Phase Transformer Turns Ratio Tester

  • Product No:TRT63 Series
  • Manufacturer:IBEKO Power AB (DV-Power)
  • Test voltages from 1 to 250 V AC

  • Turns ratio range 0,8 – 50 000

  • The best turns ratio accuracy of 0,03%

  • Single-phase test voltage

  • True three-phase test voltage

  • Automatic vector group detection

  • Built-in tap changer control unit

  • Detailed analysis of test results using DV-Win software

  • Interchangeable test leads with Three-phase Winding Ohmmeters & Tap Changer Analyzers TWA

TRT63 is a true three-phase, fully automatic test set specially designed for turns ratio, phase shift, and excitation current measurements of power, distribution and instrument transformers. TRT63 determines the transformer turns ratio by applying voltages across high voltage windings, accurately measuring voltages across the unloaded transformer windings, and then displaying the ratio of these voltages.

TRT63 is based on a state of the art technology, using the most advanced technique available today. The test set can be used to test single-phase and three-phase transformers, both with and without taps in accordance with the requirements of the IEC 60076-1 standard.

For a three-phase measurement, the test set is connected to all the three phases of a transformer to be tested. If specific vector diagrams are selected for different types of transformers, the TRT63 will run a specific test for each transformer type (i.e., single phase, Delta to wye/star, Wye/Star to delta, Delta to delta, Wye/Star to wye/star, Delta to zig-zag,etc.) without a need to switch the test hookup cables. In addition, it can perform the test with true three-phase test voltage, allowing testing any transformer type. Following the test, it displays a turns ratio, phase shift, and excitation current obtained with single-phase and/or true three-phase tests.

TRT63 lets users enter a transformer’s nameplate voltages for the turns ratio deviation calculation. This feature eliminates any error otherwise caused by an operator’s manual calculation. The TRT63 also compares the test result with the nameplate ratio and prints out the % of error for each test.

Operating conditions messages or error messages identify incorrect test conditions, abnormal operating condition or transformer problems. TRT63 has a very high ability to cancel electrostatic and electromagnetic interference in HV electric fields. It is achieved by a very efficient filtration. The filtration is made utilizing the proprietary hardware and software design solutions.


Mains Power Supply

Connection: according to IEC/EN60320-1; UL498, CSA 22.2

Mains supply: 90 – 264 V AC, 50/60 Hz or 110 – 350 V DC

Input power: 250 VA

Fuse: 2 A / 250 V, type F, not user replaceable

Output Data

Instrument / Test voltages

TRT63A

1, 8, 40, 100, 250   V AC

3 x (1, 8, 40,   100, 250)3 V AC

TRT63B

1, 10, 40, 100,   250 V AC

3 x (1, 10, 40,   100, 250)3 V AC

TRT63C

1, 8, 40, 80, 250   V AC

3 x (1, 8, 40, 80,   250)3 V AC

Measurement

Turns ratio measuring range: 0,8 – 50 000

Turns ratio resolution: 5 digits

Typical turns ratio accuracy:

@250 V AC

@80 or 100 V   AC

0,8 – 999:   ±0,03%

0,8 – 999:   ±0,05%

1 000 – 3   999: ±0,05%

1 000 – 3   999: ±0,05%

4 000 – 14   999: ±0,05%

4 000 – 14   999: ±0,1%

15 000 – 19   999: ±0,05%

15 000 – 19   999: ±0,2%

20 000 – 50   000:±0,1%

20 000 – 50   000:±0,25%

 

@40 V AC

@8 or 10 V   AC

0,8 – 999:   ±0,05%

0,8 – 999:   ±0,05%

1 000 – 3   999: ±0,1%

1 000 – 3   999: ±0,1%

4 000 – 14   999: ±0,2%

4 000 – 15   000: ±0,2%

15 000 – 20   000: ±0,3%

@1 V AC

0,8 – 999: ±0,05%

1 000 – 4 000: ±0,1%

Excitation current range: 0 – 2 A

Excitation current resolution: 0,0000 – 9,9999 mA 0,1 μA 10,000 – 99,999 mA 1 μA 100,00 – 999,99 mA 10 μA 1,0000 – 2,0000 A 100 μA

Typical excitation current accuracy: ±(0,25% rdg + 500 μA)

Phase angle range: 0 – 360º

Phase angle resolution: 0,01º

Typical phase angle accuracy: ±0,05º

Display

LCD screen 20 characters by 4 lines;

LCD display with backlight, visible in bright sunlight

Interface

USB (standard)

RS232 (optional)

Data Storage

TRT63 can store up to 10 000 test results

Environmental Conditions

Operating temperature: -10 ºC – +55 ºC / 14 ºF – +131 ºF

Storage & transportation: -40 ºC – +70ºC / -40 ºF – +158 ºF

Humidity: 5% – 95% relative humidity, non condensing

Dimensions and Weight

Dimensions (W x H x D): 480 x 190 x 385 mm / 18.9 x 7.48 x 15.16 in

Weight: 9 kg / 19.8 lbs

Warranty:3 years