Transformer tap Changer Analyzer & Winding Ohmmeter

  • Product No:RMO-TD Series
  • Manufacturer:IBEKO Power AB (DV-Power)

The controer Analyzer & Winding Ohmmeter of the RMO-TD series is designed for winding resistance measurement of inductive objects, and for a tap changer analysis. The RMO-TD series is based on the state of the art technology, using the most advanced switch mode technology available today. The RMO-TD series is accurate (0,1_%), powerful (up to 60 A) and lightweight. It generates a true DC ripple free current with automatically regulated measure-ment and discharging circuit.

RMO-TD series can perform a simple, quick and reliable transformer on-load tap changer condition assessment. This series enables measurements of a winding resistance in every tap position, current ripple values (percentage of a current drop during a tap change) and transition times during the tap changes. Problems with a connection, contacts, and selector/diverter switch operation (tap change with interruption) can be detected with these measurements.

  • On-load tap changer dynamic resistance measurement 

  • Three resistance measurement channels 

  • One temperature measurement channel 

  • Automatic resistance measurement  

  • Heat Run test 

  • Rapid automatic demagnetization 

  • Tap changer motor current monitoring channel 

  • Automatic discharge circuit 

  • Built-in tap changer control unit 

  • Three models: RMO25TD, RMO40TD, RMO60TD


Winding Resistance Measurement

  • Test currents:   

    5 mA – 25 A DC for RMO25TD  

    5 mA – 40 A DC for RMO40TD  

    5 mA – 60 A DC for RMO60TD

  • Output voltage: up to 55 V DC 

  • Measurement range: 0,1 μΩ – 10 kΩ 

  • Typical accuracy:

    ±(0,1% rdg + 0,1% F.S.) for 0,1 μΩ-1,999 kΩ range

    ±(0,2% rdg + 0,1% F.S.) for 2 kΩ - 10 kΩ range

Resolution

  • 0,1 μΩ – 999,9 μΩ: 0,1 μΩ 

  • 1,000 mΩ – 9,999 mΩ: 1 μΩ 

  • 10,00 mΩ – 99,99 mΩ: 10 μΩ 

  • 100,0 mΩ – 999,9 mΩ: 0,1 mΩ 

  • 1,000 Ω – 9,999 Ω: 1 mΩ 

  • 10,00 Ω - 99,99 Ω: 10 mΩ 

  • 100,0 Ω – 999,9 Ω: 0,1 Ω 

  • 1,000 kΩ – 9,999 kΩ: 1 Ω

Data Storage

  • 1 000 internal memory positions 

  • USB flash drive feature enables storage of a huge number of measurements

Printer (optional)

  • Thermal printer 

  • Paper width 80 mm

Temperature Measurement

  • One temperature measurement channel Thermometer Pt100

    -50 ºC +180 ºC / -58 ºF +356 ºF 

    50 mm x 6 mm 

OLTC Dynamic Resistance Measurement

  • Sampling rate: 0,1 ms 

  • Automatic open circuit detection and warning 

  • Transition current ripple measurement 

  • Transition time measurement using DV-Win  software 

  • Timing measurement of different transition  changes using DV-Win graph analysis tool

AC Current Measurement Channel

  • Resolution: 0,1 ms 

  • Amplitude resolution: 16 bit

Current Clamp Meter Specifications

  • Measuring range: 30 / 300 A 

  • Nominal current: 300 ARMS or 450 A DCPK

  • Frequency range: DC to 20 kHz (-3 dB)

Computer Interface

  • USB 

  • Optional: RS232

Warranty :Three years

Environmental Conditions

  • Operating temperature:  - 10 ºC to + 55 ºC / + 14 ºF to + 131 ºF 

  • Storage & transportation:  - 40 ºC to + 70 ºC / - 40 ºF to + 158 ºF 

  • Humidity 5 % - 95 % relative humidity,  non condensing

Dimensions and Weights

  • Device                Weight                              Dimensions (WxHxD) 

    RMO25TD          10,0 kg / 22,0 lbs              480 x 197 x 395 mm (18.9 x 7.75 x 15.6 in)

    RMO40TD          13.5 kg / 29.8 lbs              480 x 197 x 395 mm (18.9 x 7.75 x 15.6 in )
    RMO60TD          14,0 kg / 30.8 lbs              480 x 197 x 395 mm (18.9 x 7.75 x 15.6 in)

Mains Power Supply

  • Connection according to IEC/EN60320-1;  UL498, CSA 22.2 

  • Mains supply: 90 V - 264 V AC 

  • Frequency: 50 / 60 Hz 

  • Mains supply voltage fluctuations up to ±10 %   of the nominal voltage 

  • Input power: 1 800 VA 

  • Fuse 15 A / 250 V, type F, not user replaceable 

Applicable Standards

  • Installation/overvoltage: category II 

  • Pollution: degree 2 

  • Low voltage directive: Directive 2014/35/EU (CE conform); Applicable standards, for a class I instrument, pollution degree 2, installation category II: IEC EN61010-1 

  • EMC:   Directive 2014/30/EU (CE Conform)     Applicable standard EN 61326-1 

  • Safety: CAN/CSA-C22.2 No. 61010-1, 2nd edition, including Amendment 1