The Calmet TE30 Analyser and Tester is used for:
• verification of power network wiring with measure and recording of power network parameters,
• calibration and testing of electricity meters and instrument transformers (CT Current Transformers and PT Potential Transformers) directly on site:
electricity meters EN 50470, IEC 62052 and IEC 62053 with accuracy relative to internal reference including measure of meter error, counter error and maximum power meter error,
instrument transformers EN 60044 including CT/PT Ratio error and phase error as well as CT/PT burden simultaneously in three phases,
• measuring, recording and analyzing of power quality.
Calmet TE30
• Measure of power network parameters in class 0.05 or 0.1
• Voltage ranges 0.05…600V and 0.1…40kV • Current ranges 0.001…12(120)(1200)(30/300/3000)A
• Testing of electricity meters and CT/PT Transformers
• Recording and analyse of power quality
• Vector, oscilloscope, bar and trend charts of three phase network
• Powering from 50…450V AC power network and internal battery with charger
• Large 7" color Touchscreen and Calmet TE30 PC soft
• Data readout and meter control via USB, Ethernet and Bluetooth
• Data storage in SD flash memory card up to 32GB
• Calibration Certificate